0-10V output calibration sequence? #39

@HudsonMC16

Description

@HudsonMC16

It's possible I'm going something wrong here, or I have uncovered a bug in the calibration logic. Can you please clarify the sequence of commands for calibrating the outputs?

$ megaind 0 uoutcalrst 1
Calibration done

$ megaind 0 uoutwr 1 1
done

$ megaind 0 uoutcal 1 1.012
Calibration in progress

$ megaind 0 uoutwr 1 9
done

$ megaind 0 uoutcal 1 9.02
Calibration done

$ megaind 0 uoutwr 1 0
done

$

At this point, the output was reading 5.297V. I've tried various sequences and values for the calibration points, and either get a cal curve with double the slope it should have or calibration errors. Thoughts?