TM221 PLC Python Toolkit

Real-time data acquisition, logging, and visualization for the Schneider Electric Modicon TM221CE16R programmable logic controller over Modbus TCP.

Overview

This toolkit provides three Python applications for communicating with a Modicon M221 series PLC:

Script Purpose
process_monitor.py Real-time data acquisition, CSV logging, and live trend dashboard
plc_terminal.py Interactive command-line shell for reading/writing PLC registers
find_plc.py Network scanner to locate M221 PLCs on the 10.10.x.x subnet

The applications use Modbus TCP (port 502) over the PLC's built-in Ethernet port. No proprietary software or drivers are required on the monitoring side — only Python and the open-source pymodbus library.

Hardware Requirements

  • PLC: Schneider Electric Modicon TM221CE16R (or any M221 series controller with Ethernet)
  • Power: 100–240 VAC to the PLC's L/N terminals
  • Network: Standard Ethernet cable (Cat5e or Cat6) — direct PC-to-PLC or through a switch
  • 24VDC supply (optional): Required only if testing physical I/O (digital inputs, analog sensors, output indicators)

Software Requirements

  • Python 3.8+
  • pymodbus (required)
  • matplotlib (optional — enables the graphical dashboard; falls back to console mode without it)
pip install pymodbus matplotlib

Note on pymodbus versions: This project uses pymodbus 4.x API conventions (device_id= parameter). If you are on pymodbus 3.x, replace device_id= with slave= in all Modbus calls. If you are on pymodbus 2.x, replace it with unit=.

Quick Start

1. Find Your PLC's IP Address

The M221 defaults to 10.10.x.y, where x and y are derived from the last two bytes of the MAC address printed on the front label.

Manual calculation: If the MAC is 00:00:54:6A:27:DC, the last two bytes are 27 and DC. Converting hex to decimal: 0x27 = 39, 0xDC = 220. The default IP is 10.10.39.220.

Automatic discovery:

python find_plc.py

2. Configure Your PC's Network

Set your Ethernet adapter to a static IP on the same subnet:

Setting Value
IP Address 10.10.39.50 (or any unused address in 10.x.x.x)
Subnet Mask 255.0.0.0
Gateway (leave blank)

Verify connectivity:

ping 10.10.39.220

3. Download a PLC Program

The M221's Modbus registers are not allocated until a program has been downloaded. Use EcoStruxure Machine Expert – Basic (free, Windows only) to create and download at least a minimal program. Without a loaded program, all Modbus reads will return "Illegal Data Address" (exception code 2).

4. Run the Monitor

# Full dashboard (requires matplotlib + display)
python process_monitor.py --ip 10.10.39.220

# Console-only mode (no GUI required)
python process_monitor.py --ip 10.10.39.220 --headless

# Custom polling interval and run duration
python process_monitor.py --ip 10.10.39.220 --interval 0.5 --duration 3600

Process Monitor

process_monitor.py connects to the PLC, polls configured tags at a fixed interval, logs every sample to daily CSV files, and renders a live six-panel trend dashboard.

Simulated Process: Mixing Tank

The default configuration monitors a mixing tank with the following I/O:

Analog Inputs (sensors)

Tag Register Raw Range Unit Eng. Range
Temperature %IW0 0–1000 °C 0.0–100.0
Pressure %IW1 0–1000 bar 0.0–10.0
Tank Level %IW2 0–1000 % 0.0–100.0
Flow Rate %IW3 0–1000 L/min 0.0–50.0

Digital Outputs (actuators)

Tag Address
Heater %Q0.0
Mixer Motor %Q0.1
Inlet Valve %Q0.2
Outlet Valve %Q0.3

Holding Registers

Tag Address Purpose
Temperature Setpoint %MW0 Operator setpoint (written by HMI/SCADA)
Pressure Setpoint %MW1 Operator setpoint
Alarm Word %MW10 16-bit packed alarm flags
Cycle Counter %MW20 PLC scan counter

Alarm Bits (%MW10)

Bit Alarm
0 Over_Temp
1 Over_Pressure
2 Low_Level
3 High_Level
4 Flow_Fault
5 Heater_Fault
6 Motor_Fault
7 E_Stop

Command-Line Arguments

Argument Default Description
--ip 10.10.39.220 PLC IP address
--port 502 Modbus TCP port
--slave 1 Modbus slave/unit ID
--interval 1.0 Polling interval in seconds
--duration 0 (forever) Run time in seconds; 0 = infinite
--headless false Disable GUI; console and CSV only
--logdir logs Directory for CSV log files
--history 300 Max data points retained in chart

CSV Output

Log files are created daily in the --logdir directory with automatic rotation at midnight:

logs/
├── process_log_2026-04-28.csv
├── process_log_2026-04-29.csv
└── ...

Each row contains a timestamp (millisecond resolution), all analog values in engineering units, digital output states (0/1), the alarm word in hex, and the PLC cycle counter.

Customizing for Your Process

All process-specific configuration lives in four tag tables at the top of process_monitor.py. To adapt the monitor for a different process, edit these tables — no other code changes are needed:

ANALOG_TAGS = [
    # (name, register_type, address, scale_min, scale_max, unit, eng_min, eng_max)
    ("My_Sensor", "input", 0, 0, 4095, "psi", 0.0, 150.0),
]

PLC Terminal

plc_terminal.py provides an interactive command-line shell for manual register access, real-time monitoring, and diagnostics.

pip install pymodbus rich   # rich is optional, adds colored tables
python plc_terminal.py

Commands

Connection

connect tcp 10.10.39.220     Connect via Modbus TCP
connect rtu /dev/ttyUSB0     Connect via Modbus RTU (serial)
disconnect                   Close connection
slave <id>                   Set Modbus slave ID

Reading

ri  [start] [count]          Read discrete inputs (%I)
rq  [start] [count]          Read coils / outputs (%Q)
rmw [start] [count]          Read holding registers (%MW)
riw [start] [count]          Read input registers (%IW)
rfloat <register>            Read 32-bit float from two registers

Writing

wq  <addr> <0|1>             Write a single coil
wmw <start> <val> ...        Write holding register(s)
wfloat <reg> <value>         Write 32-bit float to two registers
toggle <addr>                Toggle a coil on/off

Tools

scan                         Full I/O snapshot
monitor <mw|i|q> [start] [count]   Live-watch values (Enter to stop)
dump [start] [count]         Hex dump of registers

PLC Finder

find_plc.py scans the network for devices with Modbus TCP (port 502) open, then attempts to identify each one by reading registers and querying the Modbus Device Identification object.

python find_plc.py                                         # Full 10.10.x.x scan
python find_plc.py --start 10.10.39.1 --end 10.10.39.254  # Narrow scan
python find_plc.py --timeout 0.3 --workers 1000            # Faster scan

Network & Wiring

Ethernet Connection

Connect a standard Ethernet cable between your PC and the PLC's RJ45 port. Modern hardware auto-negotiates, so a regular straight-through patch cable works — no crossover cable needed.

PLC Default IP Address

The M221 defaults to 10.10.x.y with a 255.0.0.0 subnet mask, where x.y is derived from the last two bytes of the MAC address on the front label. If a DHCP server is configured but unreachable, the PLC falls back to this address.

To confirm the IP via packet capture:

# Listen for ARP announcements from the PLC (replace en0 with your interface)
sudo tcpdump -i en0 -n ether host <PLC_MAC_ADDRESS>

Power

The TM221CE16R accepts 100–240 VAC on its L/N terminals. For benchtop testing, wire a standard appliance cord to the terminals and plug it into a switched power strip. A separate 24VDC supply is needed only for powering I/O circuits (sensors, input simulation switches, output indicator LEDs).

M221 Modbus Address Map

All addresses are 0-based (pymodbus convention).

PLC Variable Modbus FC Address Direction Description
%M0%M255 FC 1/5/15 0–255 Read/Write Memory bits (coils)
%M0%M255 FC 2 0–255 Read Memory bits (discrete inputs)
%MW0%MW255 FC 3/6/16 0–255 Read/Write Memory words (holding registers)
%MW0%MW255 FC 4 0–255 Read Memory words (input registers)
%Q0.0%Q0.15 FC 1 128–143 Read Physical outputs
%I0.0%I0.15 FC 2 128–143 Read Physical inputs

Important: Physical I/O (%I, %Q, %IW) is accessible at offset addresses, not at address 0. To make physical I/O readable at convenient addresses, copy them into %MW registers in the PLC program.

Troubleshooting

Symptom Likely Cause Fix
Connection timed out Wrong IP or subnet mismatch Verify IP with find_plc.py or tcpdump; check your PC's static IP is on the same subnet
Connection refused Modbus TCP disabled Enable in EcoStruxure Machine Expert – Basic under Ethernet settings
Exception code 2 (Illegal Data Address) No program loaded, or wrong register address Download a program to the PLC; verify address mapping
unexpected keyword argument 'slave' pymodbus version mismatch Use device_id= (v4.x), slave= (v3.x), or unit= (v2.x)
Dashboard doesn't appear matplotlib not installed pip install matplotlib; runs in headless mode without it
Ping works but Modbus fails Port 502 blocked or PLC in fault state Test with nc -zv <ip> 502; check PLC ERR LED

Project Structure

├── process_monitor.py        # Data acquisition, logging, and dashboard
├── plc_terminal.py           # Interactive register read/write shell
├── find_plc.py               # Network scanner for M221 PLCs
├── docs/
│   ├── dashboard_screenshot.png
│   ├── tm221_guide.docx      # Development & configuration guide
│   └── five_patterns_article.docx
├── logs/                     # CSV data files (created at runtime)
└── README.md

License

GPL-3.0 license