EDP Interface Plates 🔩📐

interface plates that mount to container end walls and organize all inter-module connections

Architecture Context

rectangle container_a
rectangle container_b
rectangle plate_a
rectangle plate_b
rectangle flexible_assembly

container_a -r- plate_a: receiver frame (welded)
container_b -l- plate_b: receiver frame (welded)
plate_a -r- flexible_assembly: liquid-tight conduit\nM12 connectors\ncooling QDs
flexible_assembly -r- plate_b

Containers are placed face-to-face. Plates mate as a pair via flexible assemblies — there is no hard-dock interface. Containers tolerate ±25mm horizontal and ±10mm vertical misalignment, absorbed by hose/cable service loops.

Plate Variants

Six variants cover all module-adjacency combinations. Variant codes follow [Module A]-[Module B]-[String/Port Count] where applicable.

Variant Used When Carries Plate Codes
BG Grid Module present DC power, grounding, data BG-2, BG-4, BG-8 (per BESS string count)
BB N_BESS > 1 Data + grounding only (no DC) BB (fixed)
CT Always (1:1 Compute:Thermal) Cooling fluid + sensor data CT (QD port size [OPEN] pending GPU vendor DLC spec)
CG Grid Module present AC feeder + data CG (fixed, conduit sized from sizing engine Module F)
CB grid_connection == 'none' Off-grid AC feeder + data CB (variant of CG)
EX All deployments External services on long wall EX-T, EX-G, EX-B, EX-C (per module type)

See the spec doc for full penetration schedules per variant.

Material & Finish

Parameter Standard Defense (deployment_context == defense_forward | sovereign_government)
Outer dimensions 640mm × 840mm same
Thickness 6mm 10mm
Material 6061-T6 aluminum (ASTM B209) 5083-H116 marine grade (ASTM B209)
Finish Type II anodize 15–25 μm (MIL-A-8625) Type III hard anodize 40–60 μm
IP rating IP55 IP65 (verified per MIL-STD-810H Method 506)
Secondary seal none 10mm closed-cell EPDM backer
Fasteners Zn-plated steel M10 (ASTM F593 G1) 316 SS M10 (ASTM F593 G2)

Output Artifacts

For every plate variant required by a deployment, the implementation outputs:

  1. DXF file — 2D fabrication drawing with plate outline, all hole/cutout locations dimensioned from plate center, gasket groove cross-section, mounting hole pattern with thread callouts, ARCNODE title block (part number, variant code, revision, material spec, finish spec).
  2. BOM line item — structured JSON referencing the drawing:
    {
      "part_number": "ARC-PLT-BG4-001",
      "description": "Interface Plate, BESS-to-Grid-Module, 4-String",
      "qty": 1,
      "material": "6061-T6 aluminum",
      "finish": "Type II anodize",
      "drawing_ref": "ARC-PLT-BG4-001.dxf",
      "type": "custom_fabrication"
    }
  3. Penetration schedule — table of every hole/cutout: penetration ID, X/Y center coordinates from plate origin, diameter or W×H, fitting spec, OTS part number.

Part Numbering

ARC - PLT - [VARIANT CODE] - [REVISION]

Examples:
  ARC-PLT-BG2-001    BESS-Grid, 2-String
  ARC-PLT-BG4-001    BESS-Grid, 4-String
  ARC-PLT-BG8-001    BESS-Grid, 8-String
  ARC-PLT-BB-001     BESS-BESS daisy chain
  ARC-PLT-CT-001     Compute-Thermal           [OPEN: QD port size]
  ARC-PLT-CG-001     Compute-Grid
  ARC-PLT-CB-001     Compute-BESS (off-grid)
  ARC-PLT-EX-T-001   External services, Thermal Module
  ARC-PLT-EX-G-001   External services, Grid Module
  ARC-PLT-EX-B-001   External services, BESS Module

Defense variants append `-D`:
  ARC-PLT-BG4-001-D

Toolchain

The fabrication flow is CadQuery-based:

parametric model.py (CadQuery) → STEP → DXF + GD&T drawing → BOM line item + penetration schedule
uv sync
uv run poe build              # CadQuery → STEP per variant
uv run poe validate-model     # BRep validity + bbox vs spec
uv run poe generate-drawings  # DXF + GD&T PDF per variant
uv run poe sim                # IP rating verification fixtures

Open Design Parameters

# Parameter Impact
1 GPU vendor DLC loop architecture CT plate QD port size and count
2 Off-grid inverter location CB variant applicability
3 4,160V AC option CG conduit sizing changes significantly at MV
4 Dry cooler pipe connection size EX-T plate flange size
5 MV grid cable entry EX-G plate penetration sizing

About

Parametric CadQuery CAD source for inter-container interface plates

Topics

Resources

Stars

Watchers

Forks

Releases

No releases published

Packages

 
 
 