FlushWaterNG

Sump pump controller for the Seeed XIAO ESP32-C3. Reads a resistive water level sender, decides when the pump may run, and reports to MQTT / Home Assistant.

The pump is not driven directly — the relay inhibits or allows it, so the pump's own float switch remains the final authority.

Behaviour

Condition to allow the pump
Night (22:00–04:59) level > waterLevelThreshold (5 cm)
Day (05:00–21:59) level > criticalWaterLevel (32 cm) or rising ≥ 1.0 cm/min
Always required MQTT has not published no to the safety topic
Refractory 5 min lockout after each window — bypassed when critical
Window 5 min max, closes early once drained (min 30 s)

Two failure directions are deliberate: an unknown clock falls back to night rules so a network outage cannot disarm flood protection, and a critical level bypasses the refractory so a real flood is not locked out half the time.

Status LED

One LED, counted blink codes — N pulses, then a long dark gap.

LED Meaning
Dark All good — nothing needs your attention
Solid on Pump allowed right now
2 blips No WiFi
3 blips WiFi up, no MQTT broker
4 blips Connected, clock not NTP-synced
5 blips MQTT reported unsafe to operate
6 blips Sender table malformed — pump forced allow

Hardware

Seeed XIAO ESP32-C3, a resistive level sender (240 Ω empty → 33 Ω full, the standard automotive range), and a relay module on its own supply.

SUPPLY --[ R_TOP ]--+-- node --[10k]--+-- D1 (ADC)
                    |                 |
                [ sender ]         [100nF]
                    |                 |
                   GND               GND
XIAO pin Function
D1 Divider node, via 10k series + 100nF to GND
D10 Relay inhibit/allow, 10k pull-up to 3V3
D5 Status LED anode → 220 Ω → GND

Non-negotiable details:

  • ADC1 only. D0/D1/D2 work; D3 is ADC2 and returns garbage while WiFi runs.
  • BAT54 Schottky from D1 to 3V3. An open sender pulls the node to the full supply; the 10k plus the clamp keeps that off the GPIO.
  • 10k pull-up on D10. INHIBIT_ACTIVE_LEVEL is HIGH, so a floating-low pin at boot means pump allowed — the wrong failure direction. Internal pull-ups are inactive during reset.
  • 5V pin or USB, never both. That pin is USB VBUS.

Build

PlatformIO:

cp src/config.example.h src/config.h   # then fill in your credentials
pio run -t upload
pio device monitor

src/config.h is git-ignored and must never be committed.

Arduino IDE also works — copy src/main.cpp to FlushWaterNG.ino alongside config.h, select board XIAO_ESP32C3 and set USB CDC On Boot: Enabled. Without that setting Serial is routed to the GPIO20/21 UART, which is not wired to the USB-C connector, and the monitor stays silent. The source carries explicit forward declarations, so it compiles as either .ino or .cpp.

Calibration

Level is looked up by sender resistance, not ADC counts, so the table survives a change of supply voltage, top resistor, or chip.

  1. Measure SUPPLY_MV and R_TOP_OHM with a meter — on the supply you will actually run on. USB VBUS and an external brick do not read the same.
  2. Set CALIBRATION_VERBOSE 1 and log resistance against known water heights.
  3. Replace senderTable[]. It must be strictly ascending in resistance and descending in level; validateSenderTable() checks this at boot and fails the pump to allowed if it does not hold.

The sender is not linear — roughly 3.5 Ω/cm through the main body but ~12 Ω/cm below 7 cm. Keep the dense rows at the bottom; that is where the decisions are.

MQTT

Topic Direction Payload
pool/sumppump/safe in no inhibits the pump; anything else allows it
pool/sumppump/status out, retained allow / inhibit
pool/sumppump/level out level in cm
pool/sumppump/alert out sensor faults, ineffective pump, expired safety hold
pool/sumppump/log out boot and 5-minute heartbeat diagnostics

A no on the safety topic expires after 30 minutes without a broker update and fails open. A latch that can never be cleared is a flood waiting to happen.

Home Assistant

Copy the entities from configuration.yaml into your HA config and restart. The broker needs a matching login — see src/config.example.h.

You get:

Entity What it is
sensor.sump_water_level Level in cm, graphable
binary_sensor.sump_pump_allowed Whether the pump may run right now
switch.sump_safety_hold Turn on to inhibit the pump
sensor.sump_last_alert Sensor faults, ineffective pump, expired hold
sensor.sump_diagnostics Boot line and 5-minute heartbeat
binary_sensor.sump_controller Whether the controller is alive at all

Availability. The controller publishes online retained to pool/sumppump/availability, and registers an MQTT Last Will so the broker publishes offline by itself if the controller stops answering keepalives. Every entity hangs off that topic, so a dead ESP shows as unavailable rather than silently holding its last reading — which, for a water level, would look exactly like a calm sump. Expect ~45 s of lag; the will fires after 1.5× the 30 s keepalive.

lovelace-flushwater.yaml has a dashboard card with the level history and pump state overlaid.

Add the automations too:

automation: !include automations.yaml

How the persistent hold works. Turning the switch on publishes no, but the controller drops that hold after 30 minutes without a further message — a latch nothing can clear is a flood waiting to happen. So HA re-publishes it every 10 minutes, and a hold you set on purpose lasts indefinitely.

The two halves matter together: as long as HA is alive the hold sticks, and if HA or the broker dies the hold lapses within 30 minutes and the controller goes back to protecting the basement on its own. The 10-minute interval tolerates two consecutive missed runs. Don't widen it much — at 25 minutes a single missed run releases the pump.

automations.yaml also notifies on any controller alert, and warns if sensor.sump_diagnostics goes quiet for 20 minutes. The heartbeat is every 5, so silence means the controller is down and the pump is running unsupervised on its own float switch.

Resilience

  • Task watchdog on the loop task, 60 s.
  • Connectivity watchdog: reboot after 15 min offline, since the task WDT cannot catch a wedged network stack — loop() keeps running and feeding it. Defers while a flush is in progress.
  • Reset reason reported at boot and in heartbeats. Watch for BROWNOUT: a pump motor starting sags a shared supply and otherwise looks like a random reboot.